Open HSI menu
Subscribe Login

Home / Articles and Press Releases / Article / Hazard of Electric Arc Flash Explained

CATEGORIES

  • Latest Issue
  • Above The Neck Protection
  • Chemical Protection
  • Confined Space
  • Construction
  • Emergency Procedures
  • Energy, Oil and Mining Industries
  • Eye Protection
  • Fall Protection
  • Gas Detection
  • Hand Protection
  • Hazardous and Explosive Atmospheres
  • Health and Safety Awareness
  • Hearing Protection
  • Heat and Flame
  • Lighting and ATEX
  • Noise Monitoring
  • Personal Protective Equipment
  • Respiratory Protection
  • Safety Footwear
  • Safety Technology
  • Safety Training
  • Slips, Trips and Falls
  • Wellbeing at Work
  • Working at Height
  • Working Rights

MORE

  • Press Releases
  • Events
  • Videos
  • Webinars
  • Magazines

COMPANY

  • About
  • Advertising
  • Newsletter
  • Contact
Open HSI menu
Subscribe

Home / Articles and Press Releases / Article / Hazard of Electric Arc Flash Explained

CATEGORIES

  • Latest Issue
  • Above The Neck Protection
  • Chemical Protection
  • Confined Space
  • Construction
  • Emergency Procedures
  • Energy, Oil and Mining Industries
  • Eye Protection
  • Fall Protection
  • Gas Detection
  • Hand Protection
  • Hazardous and Explosive Atmospheres
  • Health and Safety Awareness
  • Hearing Protection
  • Heat and Flame
  • Lighting and ATEX
  • Noise Monitoring
  • Personal Protective Equipment
  • Respiratory Protection
  • Safety Footwear
  • Safety Technology
  • Safety Training
  • Slips, Trips and Falls
  • Wellbeing at Work
  • Working at Height
  • Working Rights

MORE

  • Press Releases
  • Events
  • Videos
  • Webinars
  • Magazines

COMPANY

  • About
  • Advertising
  • Newsletter
  • Contact

CATEGORIES

  • Article
  • Press Release
  • Above The Neck Protection
  • Chemical Protection
  • Confined Space
  • Construction
  • Emergency Procedures
  • Energy, Oil and Mining Industries
  • Eye Protection
  • Fall Protection
  • Gas Detection
  • Hand Protection
  • Hazardous and Explosive Atmospheres
  • Health and Safety Awareness
  • Hearing Protection
  • Heat and Flame
  • Lighting and ATEX
  • Noise Monitoring
  • Personal Protective Equipment
  • Respiratory Protection
  • Safety Footwear
  • Safety Technology
  • Safety Training
  • Slips, Trips and Falls
  • Wellbeing at Work
  • White Papers
  • Working at Height
  • Working Rights

Article

Hazard of Electric Arc Flash Explained

By Elaina Harvey

| Read Bio

Published: October 11th, 2011

Share this article

On October 10, 2008, at a cement production plant in the UK, electrical engineer Paul Ridings, 39, was engulfed by a fireball. He was investigating a fault with an energy meter when he inadvertently disturbed a loose connection and exposed a strand of wire leading to an electrical explosion.

His clothes caught fire and he sustained burns to his face, neck, chest, arms and hands. He received emergency treatment and spent 19 days in hospital. Since the incident he has undergone numerous skin grafts and operations to remove scar tissue.

An investigation by the UK’s Health and Safety Executive (HSE) found the company failed to ensure electrical systems were maintained in such a way as to protect workers. The company admitted breaching sections 2(1) and 3(1) of the Health and Safety at Work etc Act, 1974, was fined £130,000 and ordered to pay costs of £29,742.

Electrical flashover, or arc flash, is one of the most deadly and least understood hazards of electricity and is prevalent in most industries. It is widely recognised that the higher the voltage of an electrical power system, the greater the risk for people working on or near energised conductors and equipment.

The thermal energy from arc flash, however, can actually be worse and more common at lower voltages and can cause devastating, severe burn injury, and even death.

What is an electric arc flash?

An arc flash is usually caused by inadvertent contact between an energised conductor such as a bus bar or wire with another conductor, or an earthed surface. When this occurs, the resulting short circuit current will melt the conductors, ionise the air and create a conducting plasma fireball with temperatures in the core of the arc that can reach upwards of 20,000 degrees centigrade. Severe injury and even death can not only occur to persons working on the electrical equipment, but also to people located nearby.

Arc flash injury can include external burns to the skin, internal burns from inhaling hot gases and vaporised metal, hearing damage, eye damage such as blindness from the ultraviolet light of the flash, as well as many other devastating injuries.

Depending on the severity of the arc flash, an explosive force known as an arc blast may also occur, which can result in pressures of more than 100 kiloPascal (kPa), launching debris such as shrapnel at speeds of up to 300 metres per second (m/s).

Survivors of such injuries may require extensive treatment and rehabilitation and the cost of these injuries can be extreme – physically, emotionally and financially. While legislation requires businesses to perform risk assessments for all work activities, electric arc risk is often overlooked because most people are unsure how to assess and manage this hazard effectively.

Legislation

It is clear from the European Council Directive 89/391/EEC (EU Workplace Health and Safety Directive) that there is an obligation on behalf of the employer to assess the level of risk involved in the workplace and the effectiveness of the precautions to be taken. For electrical work, this should include all the hazards of electricity, including the arc flash hazard and not purely shock, as is often the case.

There has been extensive research in the United States into the arc flash phenomena over many years, the result of which has been the prediction of the arc flash hazard severity. Although the hazard is the same in Europe the legislative requirements are different to those in the US.

The US model has a direct link from hazard into PPE (personal protective equipment), whereas the EU Directive, 89/391/EEC, requires employers to perform risk assessments for all hazards/tasks. The US research, however, has resulted in the creation of the IEEE 1584 Guide for Performing Arc Flash Hazard Calculations 2002. The Institute of Electrical and Electronics Engineers (IEEE) is the largest professional electrical engineering body in the world.

Most at risk organisations, workplaces and types of work

All industries have a level of risk, but there are of course those that carry a higher risk such as utilities, energy producers and providers, mining, manufacturing companies – particularly those in the food, pharmaceutical and chemical industries – hospitals, large commercial organisations, data centres, education establishments and large leisure facilities.

For low voltage work, the following list describes activities that have the potential to initiate an arc, some of which have been shown to be common causes of electrical flashover:

  • Connecting cables into live equipment
  • Testing, especially with substandard instruments and test methods
  • Testing on damaged cables and equipment – there are several known cases of arc flash due to using voltage indicators on faulted cables
  • Inspections or any interactions which involve the exposure of live voltage conductors
  • Work on or adjacent to live low voltage conductors that are insulated, but where the work may adversely affect the integrity of that insulation; examples are drilling into panels and drawing cables into cable management systems
  • Custom and practice activities such as installing or repairing equipment which is adjacent to exposed live low voltage conductors
  • Removal and replacement/insertion of components such as circuit breakers into energised panel boards and large power bus bar tap off units
  • Live underground cable jointing
  • Switching and racking out poorly maintained or legacy LV switchgear
  • Replacement of fuses and links especially onto faults

Hazard and risk

Before arc flash is considered further, it is important to be clear about some of the terms that are used. The European definition of the term hazard means anything that has the potential to cause harm. In the case of arc flash, the potential to cause harm will vary with the current that can flow in an arc; the amount of time that the arcing fault is sustained; the length of the gaps between the conductive parts which are bridged by the arc; electrodes, the confinement around the arc; the chemical compositions of the conductors and the materials around the arc, and the distance of the worker from the arc. The term risk is the chance (or likelihood), high or low, that someone might be harmed by the hazard.

Although the arc flash hazard may be high, control measures can be adopted to reduce both the hazard and also the associated risk, to as low as possible.

How to manage the hazard

The arc flash hazard needs to be determined by risk assessment, out of which the decision to work live or dead and the required precautions will be derived.

The need for risk assessment is embodied in European Law through Directive 89/391 (EU Workplace Health and Safety Directive) and the associated guidance, which identifies electrical work as a ‘high risk’ activity.

The European Agency for Safety and Health at Work defines risk assessment as the process of evaluating risks to workers’ safety and health from workplace hazards. It is a systematic examination of all aspects of work that considers:

  1. What could cause injury or harm
  2. Whether the hazards could be eliminated and, if not
  3. What preventative or protective measures are, or should be in place to control the risk

An excellent Arc Guide written by European experts is available to take the user through a step by step approach to the management of the arc flash hazard, and includes the application of the latest developments in prevention and mitigation measures.

This will always start with a dead working policy as a matter of principle and then move through a range of risk control measures before considering personal protective equipment (PPE) as a last resort to protect individuals should an arc flash occur.

Users of the guide will know that they have the tools to easily predict incident energy levels at equipment cables to be worked upon, but risk assessment is actually much more than this. The cycle matrix diagram, right, illustrates how this important step of prediction is necessarily, followed by prevention, protection and then finally, publishing.

Predict

The severity of the thermal effect of an arc flash is defined by the amount of ‘incident energy’ that a victim, standing at a given distance away from the arc, could receive to the surface of the skin. The ‘incident energy’ is the value calculated which defines the severity of the arc flash. It can be quantified in units of kiloJoule/metre2 (kj/m2), Joule/centimetre2 (J/cm2) and calories/centimetre2 (cal/cm2). One cal/cm2 is equal to 4.184 J/cm2 and is equal to 4.184 kJ/m2.

Units of cal/cm2 are most commonly used, as this is specified for PPE garment labels according to the standard IEC 61482-2.

As a frame of reference for incident energy, an exposure to heat flux of 1.2 cal/.cm2.s during one second, e.g. exposure to 1.2 cal/cm2 can produce the onset of a second degree burn to the skin. This value is used by many standards as the benchmark that defines protection against the thermal effects of arc flash and the threshold of a zone which is commonly known as the arc flash protection boundary. This is where the predicted incident energy falls to 1.2 cal/cm2.

The calculation methods in the guide are taken from the IEEE 1584 Guide for Performing Arc Flash Hazard Calculations 2002, and take into account distance to worker, arc confinement, conductor gap, voltage, prospective fault current and disconnection time. These are accurate calculators to determine prospective fault current, which is always a key element in predicting arcing current and therefore the incident energy levels. The guide includes charts and calculators that will help even when site data is limited, such as for circuit breakers and common European style fuses.

Prevent

A fundamental safety principle, which is embodied in European Legislation is to design out, eliminate or remove the hazard at its source. This leads to the conclusion that the majority of electrical tasks must be carried out with the equipment made dead.

To work dead, the electricity supply must be isolated in such a way that it cannot be reconnected, or inadvertently become live again, for the duration of the work. As a minimum, this will include the positive identification of all possible supply sources, the opening and locking of suitable isolation points by personal padlocks and for the proving dead at the point of work.

Where the arc flash hazard cannot be eliminated then suitable risk controls should be in place (preventative or protective measures). It is important to understand that the relationship between hazard identification, deciding on suitable risk controls and the decision for work to proceed is an interdependent one.

Furthermore, the physical task to be carried out on or near energised equipment is a hugely significant factor as it is usually worker activities that initiate a damaging arc flash event. To further clarify this relationship, a decision for work to proceed where there is a significant arc flash hazard cannot be taken in isolation of other factors. The level of hazard and also the availability and effectiveness of preventative or protective measures will also need to be considered.

The activities associated with the physical task can often lead to the initiation of an arc flash event. For low voltage work, see the list already cited on page 50. The list describes activities that have the potential to initiate an arc, some of which have been shown to be common causes of electrical flashover.

It must be emphasised that the guide discourages live working. While some of the activities listed are still common in industry, practices such as connecting cables into live equipment would be very difficult to justify outside the public utilities.

The likelihood of an incident is greatly enhanced by poor worker competence and ignorance of the hazards. Common to this is the dropping of non-insulated tools or fastenings, sometimes out of breast pockets in clothing. Even for competent workers the loss of concentration, distraction and human error may be factors which lead to arc flash events.

Article 6(2) of European Council Directive 89/391/EEC EU Workplace Health and Safety Directive states that where an employer implements any preventative measures, he shall do so on the basis of the principles as follows:

  1. Avoiding the risk
  2. Evaluation of risks that cannot be avoided
  3. Combatting the risks at source
  4. Adapting to the individual
  5. Adapting to Technical Progress/Information
  6. Replacing the dangerous with the non dangerous
  7. Developing a coherent overall prevention policy
  8. Giving collective protective measures priority over individual protective measures
  9. Giving appropriate instruction to employees These general principles of prevention should be considered against a hierarchy of risk controls with priority as follows:
  10. Elimination of the arc flash hazard
    1. Safe systems of work
    2. Minimisation/engineering controls
    3. Information and training
    4. PPE

All these measures should be properly monitored and reviewed and this is particularly important when considering the lower order risk controls.

Protect

Where the risk cannot be controlled by prevention or where there is a residual risk of injury, then it may be necessary to consider mitigation to prevent injury to the worker. The requirement for and suitability of mitigation techniques must form an essential element of any risk assessment.

There are many different forms of protection arrangements such as remote operations, reduction in arcing time through arc detection and rapid disconnection and thorough training in operational techniques, such as body positioning when operating equipment.

As a last line of defence, it may be necessary to consider personal protective equipment (PPE) to prevent injury to the worker. Where protection against the thermal effects becomes necessary it must be emphasised that PPE does not prevent the accident happening in the first place.

PPE used for arc flash protection includes garments made from flame resistant (FR) fabric. This fabric is designed to provide a thermal barrier and limit the incident energy exposure at the skin surface to no greater than 1.2 cal/cm2.

FR clothing is rated based on its Arc Thermal Performance Value (ATPV) in cal/cm2 or Energy Break-open Threshold (EBT) in cal/cm2 according to EN 61482-1-1 and/or on its Class 1 or 2 performance according to EN 61482-1-2, with the arc rating certified according to IEC 61482-2.

The ATPV is the limit of the incident energy up to which a material can be exposed, so that the curve of the energy transmitted through the material will remain below the Stoll curve, and without causing break-open or, more colloquially, the ATPV is the incident thermal energy that the clothing can support before that the wearer will suffer second degree burns.

To properly protect a worker, the ATPV value – or the EBT value in case that no ATPV can be determined – of the FR clothing must exceed the prospective incident energy available at a given location, at a given distance from the electric arc event.

Non FR clothing may ignite or melt at low incident energy values and once ignited will continue to burn after the electric arc has been extinguished. Burning material next to the flesh can result in serious third degree burns, even for very short durations. This means that ordinary clothing could actually become a hazard and for this reason it should be considered within the risk assessment.

Publish

The European Council Directive 92/58/EEC stipulates the minimum requirements for the provision of safety and/or health signs at work, stating that signs must be provided where hazards cannot be adequately reduced by techniques for collective protection or by measures, methods or procedures used in the organisation of work.

Signs must be standardised across Europe to reduce hazards that may be accentuated with language and cultural differences, and they must warn of any remaining significant risk, or instruct employees of the measures they must take in relation to these risks. It is very important that employees fully understand the meaning of such safety signs and are aware of the consequences of not following the warning or instruction given by the sign.

The arc flash hazard is a serious electrical risk that needs to be managed in many industrial environments and for risk assessment for workers who operate in proximity to, or on, energised electrical equipment and cables, it is essential to ensure safety and compliance with the law.

Published: 10th Nov 2011 in Health and Safety International

Share this article

ABOUT THE AUTHOR

Elaina Harvey

Connect with Elaina Harvey

Visit Website

POPULAR POSTS BY Elaina Harvey

Hsi20magazine20november202011 87 0 600 1067 - hsi -

Article

Hazard of Electric Arc Flash Explained

Get email updates

Sign up for the HSI newsletter

Keep up-to-date through the power of email with Europe's largest audited safety magazine - delivering the latest news and products to satisfy all your occupational safety needs.
  • This field is for validation purposes and should be left unchanged.

FEATURED ARTICLES

Article

 Thameslink Traffic Management Programme

Press Release

‘Working At Height’ Remains Biggest Danger

Press Release

“Uncertainty and Ignorance” Risks More Asbestos Deaths

Advertisement

SOCIAL MEDIA

HSI on Facebook

https://www.facebook.com/HSIMagazine/

Advertisement

SOCIAL MEDIA

HSI on Twitter

hsimagazine HSI Magazine @hsimagazine ·
16h

👀 Did you spot @ionscience featured on the front cover of our recent issue? It is great to have them featured throughout issue 98, advertising their Tiger XT range!

🗞️ Subscribe today!
https://www.hsimagazine.com/subscribe/#subscription-columns

#hsimagazine #IONScience #gasdetection #VOCgas #magazine #subscribe

Reply on Twitter 1622595979374481408 Retweet on Twitter 1622595979374481408 Like on Twitter 1622595979374481408 Twitter 1622595979374481408

Advertisement

SUBSCRIBE

Stay up to date with our newsletter

    • Keep up-to-date with Europe’s largest audited safety magazine

 

    • Delivering the latest news and products to satisfy all your occupational safety needs

 

This field is for validation purposes and should be left unchanged.

Subscribe

SUBSCRIBE TO HSI MAGAZINE

5 reasons to subscribe to our digital and print package

  • Stay up to date from anywhere in the world, with instant access to the latest issue straight from your phone, tablet or laptop.
  • Trust that you’re getting the best content from our range of internationally accredited authors.
  • Get full access to our archives and see how occupational safety has evolved with us over the years.
  • Enjoy our monthly newsletter curated with up-to-the-minute news and a selection of editor’s top picks.
  • Hot off the press and straight to your door – look forward to your own glossy copy of HSI, delivered five times a year
Subscribe View Subscription levels

STAY SAFE & INFORMED

Subscribe to the best health & safety articles, news, products and regulations

Find out more

Stay up to date with our newsletter

  • This field is for validation purposes and should be left unchanged.

ABOUT

  • About HSI International
  • Advertise
  • Contact Us

YOUR ACCOUNT

Sign In Register Account Subscribe to HSI

RESOURCES

Request Media Pack

CONNECT

ACCREDITATIONS

Copyright Bay Publishing 2023. All Rights reserved.

Designed & Built by:
  • Terms & Conditions
  • Privacy Policy
  • Cookie Policy
We use cookies on our website to give you the most relevant experience by remembering your preferences and repeat visits. By clicking “Accept”, you consent to the use of ALL the cookies.
Cookie settingsACCEPT
Manage consent

Privacy Overview

This website uses cookies to improve your experience while you navigate through the website. Out of these, the cookies that are categorized as necessary are stored on your browser as they are essential for the working of basic functionalities of the website. We also use third-party cookies that help us analyze and understand how you use this website. These cookies will be stored in your browser only with your consent. You also have the option to opt-out of these cookies. But opting out of some of these cookies may affect your browsing experience.
Necessary
Always Enabled
Necessary cookies are absolutely essential for the website to function properly. These cookies ensure basic functionalities and security features of the website, anonymously.
CookieDurationDescription
cookielawinfo-checbox-analytics11 monthsThis cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Analytics".
cookielawinfo-checbox-functional11 monthsThe cookie is set by GDPR cookie consent to record the user consent for the cookies in the category "Functional".
cookielawinfo-checbox-others11 monthsThis cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Other.
cookielawinfo-checkbox-necessary11 monthsThis cookie is set by GDPR Cookie Consent plugin. The cookies is used to store the user consent for the cookies in the category "Necessary".
cookielawinfo-checkbox-performance11 monthsThis cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Performance".
viewed_cookie_policy11 monthsThe cookie is set by the GDPR Cookie Consent plugin and is used to store whether or not user has consented to the use of cookies. It does not store any personal data.
Functional
Functional cookies help to perform certain functionalities like sharing the content of the website on social media platforms, collect feedbacks, and other third-party features.
Performance
Performance cookies are used to understand and analyze the key performance indexes of the website which helps in delivering a better user experience for the visitors.
Analytics
Analytical cookies are used to understand how visitors interact with the website. These cookies help provide information on metrics the number of visitors, bounce rate, traffic source, etc.
Advertisement
Advertisement cookies are used to provide visitors with relevant ads and marketing campaigns. These cookies track visitors across websites and collect information to provide customized ads.
Others
Other uncategorized cookies are those that are being analyzed and have not been classified into a category as yet.
SAVE & ACCEPT